Single-Stage Data Reading (command 06h)

The command is designed for reading of the current data: relative level, temperature, frequency. The data are transmitted with a lower byte ahead.

Command format:

Offset, bytes Field size, bytes Value Description
0 1 31h Prefix
+1 1 00h..FFh Network address of the recipient
+2 1 06h Operation code
+3 1 00h..FFh The checksum

Response format:

Offset, bytes Field size, bytes Value Description
0 1 3Eh Prefix
+1 1 00h..FFh Network address of recipient
+2 1 06h Operation code
+3 1 -128…127 Temperature in in degrees Celsius
+4 2 0000h…FFFFh Relative level
+6 2 0000h…FFFFh Frequency value
+8 1 00h..FFh Checksum

Periodic Data Output (command 07h)

Command is designed to switch on periodic data output.

After the command is processed, the sensor starts sending data periodically — level, temperature, and frequency — with the time interval prescribed by the 13h command.

Turning off of the periodic data output is performed after receipt of any true command, reset of the processor or disconnection of power power supply (if the data output mode is not istalled by default).

Command format:

Offset, bytes Field size, bytes Value Description
0 1 31h Prefix
+1 1 00h..FFh The Network address of the sender
+2 1 07h Operation code
+3 1 00h..FFh Checksum

Response format:

Offset, bytes Field size, bytes Value Description
0 1 3Eh Prefix
+1 1 00h..FFh Network address of recipient
+2 1 07h Operation code
+3 1 00h The command has been executed successfully
The command cannot be executed
+4 1 00h..FFh Checksum

Periodic data output format:

Offset, bytes Field size, bytes Value Description
0 1 3Eh Prefix
+1 1 00h..FFh The Network address of the sender
+2 1 07h Operation code
+3 1 -128…127 Temperature in in degrees Celsius
+4 2 0000h…FFFFh Relative level
+6 2 0000h…FFFFh Frequency value
+8 1 00h..FFh Checksum

Periodic Data Output Interval Adjustment (13h command)

Command is designed to set up interval of periodic data output.

Command format:

Offset, bytes Field size, bytes Value Description
0 1 31h Prefix
+1 1 00h..FFh Network address of the recipient
+2 1 13h Operation code
+3 1 0…255 Interval of the data output in seconds
+4 1 00h..FFh Checksum

Response format:

Offset, bytes Field size, bytes Value Description
0 1 3Eh Prefix
+1 1 00h..FFh The Network address of the sender
+2 1 13h Operation code
+3 1 00h The command has been executed successfully
+3 1 01h The command cannot be executed
+4 1 00h..FFh Checksum

Default Data Output Mode (command 17h)

This command determines the order of data output after the sensor is powered on or the processor is reset. After the power is on or the processor is reset, the program will send data periodically via the interface at the time interval prescribed by the 13h command.

Command format:

Offset, bytes Field size, bytes Value Description
0 1 31h Prefix
+1 1 00h..FFh Network address of the recipient
+2 1 17h Operation code
+3 1 00h No data output
+3 1 01h The data are output in binary form
+3 1 02h The data are output in character-coded form
+4 1 00h..FFh Checksum

Response format:

Offset, bytes Field size, bytes Value Description
0 1 31h Prefix
+1 1 00h..FFh Network address of the recipient
+2 1 17h Operation code
+3 1 00h The command has been executed successfully
+3 1 01h The command cannot be executed
+4 1 00h…FFh Checksum

Change Tracking of the Sensor Configuration Settings (0Fh)

The command allows to download the entire memory space containing the configuration change records for Omnicomm LLS 30160 sensor. The records format is given in the table. Only the first 5 records are fixed in the Rom, other are rewritten according to the the circular buffer rule. the remaining elements can be overwritten according to the circular buffer rule.

Command format:

Offset, bytes Field size, bytes Value Description
0 1 31h Prefix
+1 1 00h…FFh The network address of the recipient
+2 1 0Fh Operation code
+3 1 00h…FFh Checksum

Response format:

Offset, bytes Field size, bytes Value Description
0 1 3Eh Prefix
+1 1 00h…FFh The network address of the recipient
+2 1 0Fh Operation code
+3 2 00h…FFFFh The number of data bytes transmitted after the header (length)
+5 length 00h…FFh Data
+5+length 1 00h…FFh Checksum

Формат записи лога:

Offset, bytes Field size, bytes Value Description
0 4 0h…FFFFFFFFh Sequential number of the record
+4 2 0 The network address change
1 Exchange rate change
2 Nmin minimum value change
3 Nmax maximum value change
4 Filter length change
5 Automatic output mode change
6 Data output interval change
7 CNT 1 change — empty
8 CNT2 change — full
0Аh Programming the sensor
+6 4 0h…FFFFFFFFh Configuration change time (unix time)
+10 4 0h…FFFFFFFFh New parameter value
+14 1 00h…FFh Checksum

Format of response to an error:

Offset, bytes Field size, bytes Value Description
0 1 3Eh Prefix
+1 1 00h…FFh The Network address of the sender
+2 1 0Fh Operation code
+3 1 01h The command cannot be executed
+4 1 00h…FFh Checksum

Filtration Rating Setting (10h command)

This command is intended to determine the value of the filter’s length on Omnicomm LLS 30160 sensor.

Command format:

Offset, bytes Field size, bytes Value Description
0 1 3Eh Prefix
+1 1 00h..FFh Network address of the recipient
+2 1 0Fh Operation code
+3 1 00h..FFh Cheksum

Response format:

Offset, bytes Field size, bytes Value Description
0 1 3Eh Prefix
+1 1 00h…FFh The network address of the recipient
+2 1 10h Operation code
+3 16 LLS 30160¹ The name of the sensor. The type is a line constant. The value shall be set at the manufacturing plant during the PCB firmware.
+19 11 LLS 1.0.0.0¹ Designation of the program and its version
+30 1 00h…03h Data output mode
+31 1 00h…FFh Interval of measurement results output
+32 1 0…20 Filter length
+33 2 0…4095 The lower limit for changes in level
+35 2 1…4095 Upper limit for changes in level
+37 3 000000h…FFFFFFh CNT1 is the lower limit of the input signal period range
+40 3 000000h…FFFFFFh CNT2 is the upper limit of the input signal period range
+43 1 00h…FFh Checksum

¹ the name of the sensor, version number and firmware designation can be different from the given in the table.